Heat Pump Energy Strongly Depends on Fan Speed Setting

A few weeks ago I noticed that the Mitsubishi mini-split heat pumps in my house were consuming considerably more electric energy than those in my guest cottage. This applied especially to the large heat pump (15 kBtu/h) in my house living room which carries the most load.

Since then I have looked at this more closely and concluded that the excessive energy use is assocated with the fan speed settings on the heat pumps. The fans on both house heat pumps were set to Auto while the ones in the cottage were set to High (setting 4 of 5 possible manual fan speed settings). When I switched the fan mode of the house heat pumps from Auto to High their energy consumption decreased by 30-50%. That is, they supplied more heat while using less electric energy. The change was substantial.

The data that support this conclusion are convincing. The first measurements I made were to determine the heating COP for the living room heat pump. I did this 3-4 times on different days with different outside temperatures. I obtained COP numbers like 1.95, 1.15, and 1.14. This concerned me so I reached out to my installer, Dave’s Appliance. They, in turn, told me they passed my information along to Mitsubishi. In the intervening two weeks I have not heard back from either.

I don’t know why but at some point I wondered if the fan setting might be involved. Both guest cottage and house were to be unoccupied for a few days so I set the heat pumps in both to maintain an interior temperature of 60oF, 24-hours-a-day. In addition I wrote a Home Assistant automation to change the fan speed setting at midnight so that I could observe the impact of this change on energy use. I performed this experiment with the 15 kBtu/h house living room heat pump and also with the 18 kBtu/h cottage heat pump. For both heat pumps I observed similar results. The heat pumps used 40-50% less power when the fan mode was set to High as compared to when the mode was set to Auto. I also determined that the heat pump used excess power when the fan mode was set to Medium (3rd of five manual settings). I did not try any of the slower fan settings. I have confirmed similar energy savings when the fan is set to Very High (5th of five manual settings). I believe that these conclusions apply to all four of my heat pumps, though the level of savings may vary.

After I changed the living room heat pump fan speed setting to High I again measured its heating COP. This time I obtained a value of 3.7 when the outside temperature was 30oF.

I should mention that each of my four heat pumps make use of the wireless remote temperature sensor sold by Mitsubishi. It can be purchased on Amazon. In principle, this should seemlessly integrate with my heat pumps.

This seems to me to be an important result. If I were not metering (and paying attention to) my heat pump energy I would not know they are not operating efficiently. They are producing heat and the room is comfortable. Heat pump energy use is not monitored for most installations.

But energy (and associated cost and carbon) savings is the only reason to invest in heat pumps rather than inexpensive electric baseboard heaters. After all, electric base board heaters provide more stable and quieter heat and are cheaper to install. If heat pump operation does not deliver the promised savings the heating costs and carbon footprint will not meet expectations. It is quite possible that thousands of heat pump installations in New England alone are using 50% more energy than necessary because their fans are set to Auto mode. It seems to me that Mitsubishi should care.

I don’t know if this problem is related to my use of remote wireless temperature sensors, or if it also would apply even using the internal temperature sensors. (I will not be able to disconnect my remote sensors in order to test this until I return to Maine after Christmas.) It is possible that Mitsubishi software that controls the fan may be written only for the internal tempearture sensors and is not approriate when connected to a wireless temperature sensor. I have seen nothing on the Mitsubishi web site that suggests this.

I should point out that when one uses either Kumo Cloud or the remote control to change settings on the heat pumps this often changes many other heat pump parameters. For instance, if you point the remote at the heat pump and raise the temperature, the remote also sends other parameters it has saved for fan speeds, direction, etc. Someone might set the heat pump fan speed to High using the Kumo Cloud phone app, then later adjust the set temperature with the remote and inadvertently change the fan (and other) settings to those saved on the remote.

One final comment. I did find that the temperature fluctuations were smaller when the fan was in Auto mode than when the fan was set to High or Very High. So there does seem to be a tradeoff between energy savings and temperature control. Experiments continue to better quantify this.

Excessive Heat Pump Energy – Update

A few weeks ago in my post I described how one of my four Mitsubishi mini-split heat pumps was using excessive energy. Today’s post provides additional information about that. Apparently the excessive energy is by design! For background please revisit my August 12 post.

Just a quick recap — In the last three years I have had four, low-temperature, mini-split heat pumps installed on my property in Maine. The oldest of these is a 15 kBtu/h unit that is installed in my house living room. The model number for its outdoor unit is MUZ-FH15NA. The other three units were installed over the next two years. Their outdoor units have model numbers: MUZ-FS06NA, MUZ-FS18NA, and MUZ-FS06NA. (Apparently the “FS” models are improved over the “FH” models.) All four compressors use R410A refrigerant.

These units have seen minimal use since the beginning of May. On rare occasions we have used them for a bit of cooling or heating. They have simply remained in standby mode for nearly 120 days. Three of these use 3-4 W of continuous standby power but the oldest, the 15 kBtu/h unit, particularly during the night, experiences 70W power spikes every two hours or so that last for about 10 minutes. This causes this unit to use about 0.2 kWh per day more energy than the other three. For three months I have been seeking to understand what is going on.

Back in June I emailed my installer, Dave’s Appliance, questions about this performance including graphs and other details. I have always found Dave’s to be extremely helpful. They could not explain what was going on so they passed the information along to their Mitsubishi support team. A couple of months went by with no answer.

I pestered them some more. Finally, in mid-August, two technicians from Dave’s drove the 50 miles from Winthrop to my house to make measurements on the compressor while on the phone with their Portland Mitsubishi tech support. With the travel time, these guys spent a half day addressing my issue. The only measurements they made were to confirm that a certain thermistor had the correct value.

One of the techs who came to my house was Ean Laflin, the heat pump service manager with Dave’s Appliance. After he was done troubleshooting and speaking with Mitsubishi he explained that there was a 70 W heater in the compressor, and that the control board turned it on whenever the ambient temperature was below 68F. Presumably after the heater ran for 10 minutes the temperature of the thermistor rose above the set point causing the heater to turn off. (It is my impression that there is oil in this compressor, and this heater is intended to keep the viscosity of this oil low so the compressor will start easily when called upon.)

But this begs the question, why would this heater be activated when the ambient temperature ranges from 60F to 68F? I could see the need to heat the oil during the winter. But in my part of Maine from May – October the ambient temperature is usually above 68F for much of the day and usually drops below 68F late at night. For nearly four months I have not needed this heat pump yet the heater keeps using energy, night after night. The only way I can avoid this is to shut off the circuit breaker. This is obsurd!

So why doesn’t this same thing happen with my other three heat pumps? Ean tells me that the control board on these slightly newer models is shipped with a jumper that can be set so as to disable this feature — apparently this is the default setting. He can change the jumpers on the other three heat pumps so that all four of my heat pumps run this heater and waste energy. But there is no jumper to change on my Living Room heat pump to reduce its standby power to 3W like the other three heat pumps.

I conclude from this that Mitsubishi, after shipping thousands or perhaps millions of heat pumps with this control strategy determined it was not necessary and “improved” the next generation of control boards. The only way to “improve” my heat pump would be to install a new control board. I recognize this is not a cost effective way to save the $15/year wasted by this heater.

Which leads me to my last point. Each one of my four heat pumps is connected to the internet and can be controlled using the Kumo Cloud App. Why can’t Mitsubishi download updated firmware over the internet to fix this bug? Hundreds of millions of devices (phones, etc.) that only cost a few hundred dollars can receive updated firmware over the internet. Why can’t Mitsubishi figure this out for heat pumps that cost many thousands of dollars? The technology really needs to be updated.